6-38
n105 Torque Compensation Core
Loss
Register 0168
Hex
Changes during
operation
No
Setting
range
0.0 to 6,550 (W) Unit of
setting
0.1 W
(see
note 1)
Default setting See
note 2
Note 1. The value will be set in 0.1-W increments if the loss is less than 1,000 W and
1-W increments if the loss is 1,000 W or over.
Note 2. The default setting varies with the capacity of the Inverter model.
Set Values
·Set this value to the core loss of the motor in used.
·This parameter is valid in V/f control mode only.
·Normally, the default setting does not need to be changed.
·Setthevalueif the capacity ofthe motor does not coincide withthe maximum applica-
ble motor capacity of the Inverter.
Advanced Operation Chapter 6