7-25
D RUN Command (Register 0001 Hex)
Bit No. Function
0 RUN command (1: RUN)
1 Forward/Reverse (1: Reverse)
2 External fault (External fault EF0)
3 Fault reset (1: Fault reset)
4 Multi-function input 1 (1: ON)
5 Multi-function input 2 (1: ON)
6 Multi-function input 3 (1: ON)
7 Multi-function input 4 (1: ON)
8 Multi-function input 5 (1: ON)
9 Multi-function input 6 (1: ON)
10 Multi-function input 7 (1: ON)
11 to 15 Not used
Note There is an OR relationship between input from the control terminals and input
through communications. Therefore, if multi-function inputs of this register are
settoforward/stopandreverse/stop, it is possible toexecutetheRUNcommand
through the multi-function inputs. These settings are not, however, recom-
mended because these settings establish two command lines.
D Inverter Output (Register 0009 Hex)
Bit No. Function
0 Multi-function contact output (1: ON)
1 Multi-function output 1 (1: ON)
2 Multi-function output 2 (1: ON)
3 to 15 Not used
Note The settings will be enabledif multi-function outputs 1 through3 in n057through
n059aresetto18forcommunicationsoutput.Thenthecorrespondingoutputter-
minal will be turned ON and OFF through communications.
H Broadcast Message with Slave Address: 00 (00 Hex) Write
Register No.
(Hex)
Function Description
0000 Not used ---
0001 RUN command Refer to the table below.
0002 Frequency reference Set the frequency reference based on the
maximum frequency as 30,000.
0003 to 000F Not used ---
Note 1. Data can be written to registers 0001 and 0002 only.
Communications Chapter 7