7-27
Register No.
(Hex)
DescriptionFunction
0039 PID input Read based on ±1% as ±10 and a value
equivalent to the maximum frequency as
100%.
003A PID output Read based on ±1% as ±10 and a value
equivalent to the maximum frequency as
100%.
003B to 003C Not used ---
003D Communications error Refer to the following corresponding table.
003E to 00FF Not used ---
Note The fault status 2, warning status, Inverter status 2, and accumulated operating time
functions are provided for 5.5kW and 7.5kW Inverters only.
D Status Signal (Register 0020 Hex)
Bit No. Function
0 During RUN (1: During RUN)
1 Forward/reverse operation (1: Reverse operation)
2 Inverter ready (1: Ready)
3 Fault (1: Fault)
4 Data setting error (1: Error)
5 Multi-function output 1 (1: ON)
6 Multi-function output 2 (1: ON)
7 Multi-function output 3 (1: ON)
8 to 15 Not used
D Fault Status 1 (Register 0021 Hex)
Bit No. Function Bit No. Function
0 OC 8
Fj
1 OV 9 OL1
2 OL2 10 OL3
3 OH 11 Not used
4 Not used 12 UV1
5 Not used 13 UV2
6 FBL 14 CE
7
EFj, STP
15 OPR
Note When a fault results, the corresponding bit will be set to 1.
Communications Chapter 7