EasyManua.ls Logo

Omron SYSDRIVE 3G3MV - Page 266

Omron SYSDRIVE 3G3MV
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-13
Fault
display
Probable cause and remedyFault name and Meaning
OP1
(flashing)
Operation error (OPj)
(Parameter setting error)
· The values in n050 through n056 for
multi-function inputs 1 through 7 have
been duplicated.
® Check and correct the values.
OP2
(flashing)
· The V/f pattern settings do not satisfy
the following condition.
n016 n014 < n013 n011
® Check and correct the set value.
OP3
(flashing)
· The rated motor current set in n036
exceeds 150% of the rated output cur-
rent of the Inverter.
® Check and correct the set value.
OP4
(flashing)
· The frequency reference upper limit set
in n036 and the frequency reference
lower limit set in n034 do not satisfy the
following condition.
n033 n034
® Check and correct the set values.
OP5
(flashing)
· The jump frequencies set in n083 to
n085 do not satisfy the following condi-
tion.
n083 n084 n085
® Check and correct the set values.
OP9
(flashing)
· The carrier frequency set in n080 is
incorrect. An attempt was made to set a
value that is not within a permissible
range.
® Check and correct the set value.
OL3
(flashing)
Overtorque detection (OL3)
There has been a current or
torque the same as or greater
than the setting in n098 for
overtorque detection level and
that in n099 for overtorque
detection time. A fault has been
detected with n096 for
overtorque detection function
selection set to 1 or 3.
· The mechanical system is locked or has
a failure.
® Check the mechanical system and
correct the cause of overtorque.
· The parameter settings were incorrect.
® Adjust the n098 and n099 parameters
according to the mechanical system.
Increase the set values in n98 and
n099.
Maintenance Operations Chapter 8

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals