EasyManua.ls Logo

Omron SYSDRIVE 3G3MV - Page 290

Omron SYSDRIVE 3G3MV
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
9-5
Max. applicable motor
capacity (kW)
0.37 0.55 1.1 1.5 2.2 3.0 4.0 5.5 7.5
Output
specifi-
c
a
t
i
o
n
s
Rated output
capacity (kVA)
0.9 1.4 2.6 3.7 4.2 5.5 7.0 11 14
s
p
e
c
i
f
i
-
cations
Rated output
current (A)
1.2 1.8 3.4 4.8 5.5 7.2 9.2 14.8 18
Rated output
voltage (V)
3-phase 380 to 460 VAC (according to the input voltage)
Max. output
frequency
400 Hz parameter setting
Control
charac-
t
e
r
i
s
t
i
c
s
Harmonic-current
countermeasures
DC reactor (option) connection possible
c
h
a
r
a
c
-
teristics
Control method
Sine wave PWM (V/f control)
Carrier frequency
2.5 to 10.0 kHz (in vector control)
Frequency control
range
0.1 to 400 Hz
Frequency
precision
(temperature
characteristics)
Digital commands: ±0.01% (--10°C to 50°C)
Analog commands: ±0.5% (25°C ± 10°C)
Frequency setting
resolution
Digital commands: 0.1 Hz (less than 100 Hz) and 1 Hz (100 Hz or
over)
Analog commands: 0.06 Hz/60 Hz (equivalent to 1/1000)
Output frequency
resolution
0.01 Hz
Overload capacity
150% of rated output current for 1 min
External frequency
set signal
Selectable with FREQ adjuster: 0 to 10 VDC (20 kW), 4 to 20 mA
(250 W), and 0 to 20 mA (250 W)
Acceleration/de-
celeration time
0.01 to 6,000 s (Independent acceleration and deceleration time
settings)
Braking torque
Approx. 20% (125 to 150% possible with braking resistor: 2 types)
Voltage/frequency
characteristics
Set voltage vector control/user V/f pattern
Specifications Chapter 9

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals