10-2
H Function Group 1 (n001 through n049)
Param-
eter
No.
Regis-
ter No.
Name Description Set-
ting
range
Unit
of
set-
ting
Default
setting
Changes
during
opera-
tion
Ref-
er-
ence
page
n001 0101 Parameter
write-prohibit
selection/pa-
rameter ini-
tialization
Used to prohibit parameters to be
written, sets parameters, or change
the monitor range of parameters.
Used to initialize parameters to
default settings.
0: Parameter n001 is set or dis-
played. Parameters from n002 to
n079 can be displayed only.
1: Parameters from n001 to n049
(function group 1) are set or dis-
played.
2: Parameters from n001 to n079
(function groups 1 and 2) are set or
displayed.
3: Parameters from n001 to n119
(function groups 1 through 3) are
set or displayed.
4: Parameters from n001 to n179
(function groups 1 through 4) are
set or displayed.
5: Same as set to 4, but run com-
mand excepted in program mode.
6: Clears the error log.
8: Initializes parameters to default
settings in 2-wire sequence.
9: Initializes parameters to default
settings in 3-wire sequence.
10: For the USA, initializes parameter
in 2--wire sequence.
11:For the USA, Initializes parameters
in 3-wire sequence.
0 to 11 1 1 No 3--13
5-2
List of Parameters Chapter 10