10-5
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
DescriptionNameRegis-
ter No.
n010 010A Operation
selection at
Digital Opera-
tor interrup-
tion
Select whether or not to detect the
OPR error (Digital Operator connec-
tion error).
0: No (The Inverter continues operat-
ing.)
1: Yes
(Error output turns ON and the
Inverter coasts to a stop)
0, 1 1 0 No 6-41
n011 010B Maximum fre-
quency
(FMAX)
Used to set the V/f pattern as the
basic characteristic of the Inverter.
V/f control mode: set output voltage
per frequency
Vector control mode: set for torque
adjustment
50.0 to
400.0
0.1
Hz
60.0 No 5-7
n012 010C Maximum
voltage
(VMAX)
Output
voltage
n012
ignored if parameters n016 and
n014 have the same value.
0.1 to
10.0
0.1
Hz
1.5 No 5-7
n017 0111 Minimum out-
put frequency
voltage
(VMIN)
0.1 to
50.0
(0.1 to
100.0)
0.1 V 12.0
(24.0)
(see
note 2)
No 5-7
n018 0112 Acceleration/
Deceleration
time setting
(n018)
Select the acceleration or decelera-
tion time of the Inverter.
0: 0.1 s
(Less than 1,000 s: 0.1-s incre-
ments; 1,000 s or over: 1-s incre-
ments)
1: 0.01 s
(Less than 100 s: 0.01-s incre-
ments; 100 s or over: 0.1-s incre-
ments)
0, 1 1 0 No 5-27
Note 1. The values in brackets are those for 400-V-class Inverters.
Note 2. The values in brackets are those for 400-V-class Inverters.
List of Parameters Chapter 10