Time
Minimum
output
frequency
(n016)
n091 n090
0.0 to
25.5
0.1 s 0.0 No 6-29
n092 015C Stall pre-
vention
during
decelera-
tion
Used to select a function to change the
deceleration time of the motor automatically so
that there will be no overvoltage imposed on
the motor during deceleration.
0: Stall prevention during deceleration enabled
1: Stall prevention during deceleration disabled
Note Be sure to set the parameter to 1 when
the Braking Resistor Unit or a braking
resistor is used as an option.
0, 1 1 0 No 6-31
n093 015D Stall pre-
vention
level dur-
ing accel-
eration
Used to select a function to stop the
acceleration of the motor automatically for stall
prevention during acceleration.
Set the level in percentage based on the rated
current of the Inverter as 100%.
30 to
200
1% 170 No 6-32
n094 015E Stall pre-
vention
level dur-
ing opera-
tion
Used to select a function to reduce the output
frequency of the Inverter automatically for stall
prevention during operation.
Set the level in percentage based on the rated
current of the Inverter as 100%.
30 to
200
1% 160 No 6-32
n095 015F Frequency
detection
level
Used to set the frequency to be detected.
Note Theparametern57,n58andn59formul-
ti-function output mustbe setfor theout-
putoffrequencydetectionlevels1and2.
0.00
to
400.0
0.01
Hz
0.00 No 6-47
n096 0160 Overtorque
detection
function
selection 1
Used to enable or disable overtorque detection
and select the processing method after
overtorque detection.
0: Overtorque detection disabled
1: Overtorque detection only when speed
coincides and operation continues (issues
alarm)
2: Overtorque detection only when speed
coincides and output turned OFF (for
protection)
3: Overtorque always detected and operation
continues (issues alarm)
4: Overtorque always detected and output
turned OFF (for protection)
0 to 4 1 0 No 6-35
n097 0161 Overtorque
detection
function
selection 2
Select the item to detect overtorque.
0: Detected from output torque.
1: Detected from output current.
0, 1 1 0 No 6-36
List of Parameters Chapter 10