10-26
Param-
eter
No.
Ref-
er-
ence
page
Changes
during
opera-
tion
Default
setting
Unit
of
set-
ting
Set-
ting
range
DescriptionNameRegis-
ter No.
n149 0195 Pulse train
input scale
Set this parameter to the pulse train
input scale so that frequency refer-
ences can be executed by pulse train
input.
Set the maximum pulse train fre-
quency in 10-Hz increments based on
10 Hz as 1.
Note This parameter is enabled with
n004 for frequency reference
selection set to 5.
100 to
3,300
1 (10
Hz)
2,500 No 5-25
n150 0196 Multi-function
analog out-
put, pulse
train fre-
quency selec-
tion.
Select the relationship between the
pulse train output frequency and out-
put frequency.
0: 1,440 Hz at max. frequency (A
proportional relationship is applied
to frequencies less than the
maximum frequency)
1: 1x output frequency
6: 6x output frequency
12: 12x output frequency
24: 24x output frequency
36: 36x output frequency
Note This parameter is enabled with
n065 set to 1.
0, 1, 6,
12, 24,
36
1 0 No 5-42
n151 0197 RS-422/485
communica-
tions time-
over detec-
tion selection
The set value in the parameter deter-
mines whether communications time-
over detection will be performed with
“CE” displayed if there is an interval
of more than 2 s between normal
communications and how the
detected communications time-over
will be processed.
0: Detects time-over, fatal error, and
the Inverter coasts to a stop.
1: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 1.
2: Detects time-over, detects fatal
error, and the Inverter decelerates
to a stop in deceleration time 2.
3: Detects time-over, detects nonfatal
error warning, and the Inverter
continues operating.
4: No time-over is detected.
0 to 4 1 0 No 7-2
List of Parameters Chapter 10