n161 01A1 Power detec-
tion width for
probe opera-
tion switching
Set the detection width of power that
sets the Inverter into probe operation.
Set the width in percentage based on
the power to be detected as 100%.
Note Normally, the default setting
does not need to be changed.
Note The Inverter will operate with a
power detection widthof 10% if
the value is set to 0.
0 to
100
1% 10 No 6-11
n162 01A2 Power detec-
tion filter con-
stant
Set the filter time constant of the
power detection block of the Inverter
operating in probe operation.
Filter time constant (ms) = Set value
in n162 x 4 (ms)
Note Normally, the default setting
does not need to be changed.
Note The Inverter will operate with a
time constant of 20 ms if the
value is set to 0.
0 to
255
1 (4
ms)
5 No 6-12
n163 01A3 PID output
gain
Set the rate by which PID control
value is multiplied for PID control.
Note Normally, the default setting
does not need to be changed.
0.0 to
25.0
0.1 1.0 No 6-21
n164 01A4 PID feedback
input block
selection
Set the feedback input block for PID
control detection.
0: Frequency reference control
terminal for voltage input (0 to
10 V) is enabled.
1: Frequency reference control
terminal for current input (4 to
20 mA) is enabled.
2: Frequency reference control
terminal for current input (0 to
20 mA) is enabled.
3: Multi-function analog voltage input
(0 to 10 V) is enabled.
4: Multi-function analog current input
(0 to 20 mA) is enabled.
5: Pulse train reference control
terminal is enabled.
Note Make sure that the target value
input and feedback value input
do not overlap with each other.
0 to 5 1 0 No 6-21
n165 01A5 Installed
braking resis-
tor overheat-
ing protection
(see note 1)
0: Overheating protection disabled
1: Overheating protection enabled
0,1 1 0 No ---
List of Parameters Chapter 10