EasyManua.ls Logo

Omron SYSDRIVE 3G3MV - Page 48

Omron SYSDRIVE 3G3MV
348 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
2-25
H Wiring on the Input Side of the Main Circuit
D Installing a Molded-case Circuit Breaker
Alwaysconnectthepowerinputterminals(R/L1,S/L2,andT/L3)andpowersupplyviaa
molded case circuit breaker (MCCB) suitable to the Inverter.
·Install one wiring circuit breaker per Inverter.
·Choose an MCCB with a capacity of 1.5 to 2 times the Inverters rated current.
·For the MCCBs time characteristics, be sure to consider the Inverters overload
protection (one minute at 150% of the rated output current).
·IftheMCCBistobeusedincommonamongmultipleInverters,orotherdevices,setup
a sequence such that thepowersupplywill be turned OFFby a faultoutput, asshown
in the following diagram.
3-phase/
Single-phase
200 VAC
3-phase
400 VAC
Power
supply
Inverter
Fault output
(NC)
(see
note)
Note Use a 400/200 V transformer for a 400-V model.
D Installing a Ground Fault Interrupter
Inverteroutputsuse high-speedswitching,sohigh-frequency leakagecurrentisgener-
ated.
Ingeneral,aleakagecurrentofapproximately100mAwilloccurforeachInverter(when
the power cable is 1 m) and approximately 5 mA for each additional meter of power
cable.
Therefore, at the power supplyinput area, use a special-purposebreaker for Inverters,
which detects only the leakage current in the frequency range that is hazardous to
humans and excludes high-frequency leakage current.
Design Chapter 2

Table of Contents

Other manuals for Omron SYSDRIVE 3G3MV

Related product manuals