Cable length 50 m max. 100 m max. More than 100 m
Carrier frequency 10 kHz max. 5 kHz max. 2.5 kHz max.
D Single--phase motors cannot be used
Theinverterisnotsuitedforthevariablespeedcontrol ofsingle--phase motors.Single--
phase motors are either capacitor start motors or split--phase startmotors (themethod
fordeterminingrotationdirectionatstartupisdifferent).Ifacapacitorstartmotorisused,
the capacitor may be damaged by a sudden electric discharge caused by inverter out-
put. If a split--phase motor is used, the starting coil may burn because the centrifugal
switch does not operate.