3-13
H Setting n001 for Parameter Write-prohibit Selection/Parameter
Initialization
·Nodatacanbewrittenton176forparametercopyfunctionselectionunlessthedefault
setting is changed. To write data to this parameter, set n001 for parameter write-pro-
hibit selection/parameter initialization to 4.
Parame-
ter
Register Name Description Setting
range
Unit of
setting
Default
setting
Chan-
ges dur-
ing
opera-
tion
n001 0101 Parame-
ter write-
prohibit
selection/
parame-
ter initial-
ization
Used to prohibit parameters
to be written, sets parame-
ters, or change the monitor
range of parameters.
Used to initialize parameters
to default settings.
0: Sets or monitor parameter
n001. The parameters within
a range from n002 to n179
can be monitored only.
1: Sets or monitor the param-
eters within a range from
n001 to n49 (i.e., function
group 1 settings).
2: Sets or monitor the param-
eters within a range from
n001 to n79 (i.e., function
groups 1 and 2 settings).
3: Sets or monitor the param-
eters within a range from
n001 to n119 (i.e., function
groups 1 through 3 settings).
4: Sets or monitor the param-
eters within a range from
n001 to n179 (i.e., function
groups 1 through 4 settings).
5: Same operation as set to
4, but RUN command is ex-
cepted in program mode.
6: Clears the error log.
8: Initializes parameters to
default settings in 2-wire
sequence.
9: Initializes parameters in
3-wire sequence.
10:For the USA, initializes
parameter in 2--wire se-
quence.
11:For the USA, initializes
parameter in 3--wire se-
quence.
0 to 9 1 1 No
Preparing for Operation and Monitoring Chapter 3