3-20
Display RemedyProbable causeName
cpe Copy error An attempt was made to
copy or verify the parameter
set values while the
Inverters are different to
each other in voltage or
control mode.
Check that the Inverters are
the same in voltage and
control mode. If either of
them is different, no
parameter set values can be
either copied or verified.
If the Inverters are different
only in control mode, retry
after changing the mode of
the Inverter to which the
parameter set values are to
be written.
cye Copy voltage error Main-circuit low voltage is
detected while the Inverter
was copying the parameter
set values.
Retry after checking that the
voltage of the main circuit is
normal.
uae Capacity error An attempt was made to
verify the parameter set
values while the Inverters
were different to each other
in capacity.
To continue verifying the
parameter set values, press
the Enter Key.
To cancel the operation,
press the STOP/RESET
Key.
ife Communications
error
A communications error
resulted between the
Inverter and Digital
Operator.
Retry after checking the
connection between the
Inverter and Digital
Operator.
Preparing for Operation and Monitoring Chapter 3