43
Wiring Section 2-2
Connecting 2-Wire AC Sensors
A two-wire sensor cannot be connected directly to the AC input. To
connect a two-wire sensor, attach an external bleeder resistance in
the way shown below.
Example: Connecting to a CPU Unit or Expansion I/O Unit
a) Use a resistance that satisfies both of the following
conditions.
b) Because of heat generation, use a resistor with at least the
following wattage.
Note Calculating the Bleeder Resistance
when Connecting an OMRON E2E-
X10Y 2-Wire AC Sensor
This calculations in this example
are based on an input voltage of
85 to 110 V AC.
The following values are from the
Sensor datasheet.
The Sensor's maximum leakage
current is 1.7 mA.
The minimum current when the
Sensor's OFF residual voltage is
L
R
N
I0 to I5
Two-wire
sensor
Internal
circuit
R1 ()
Max. OFF-voltage for AC input (25 VAC)
Sensors max. leakage current (A)
R2 ()
Voltage supplied to sensor (V)
Min. current for which the
sensors OFF residual voltage is
less than 25 V (A)
P (W)
(
Voltage supplied
to sensor)
2
Resistance value
× 3 (allowance factor)
Output residual voltage
Load current
(
mA
)
Load residual
voltage
Load voltage VL (V)
At 100 V AC
E2E-X@Y@
ON
100 VAC
OFF