23.7 Version and Alarm Counter (H4/U7)
This menu can be used to show the following information:
Version: FT128 software / firmware version downloaded to the main board 4556.
Alarm counter: The alarm counter is increased with "1" every time the FDCIE. enters the
real "fire alarm condition" (Fire alarm indication in the display, LEDs "Fire" lit and the FDCIE
buzzer sounding), i.e. not for zones in test mode. It starts on 000 and goes to 999. It can
be reset to 000 via EBLWin (Control unit menu "Reset alarm counter…"). It is stored in an
EEPROM, i.e. the value will be retained also after the FDCIE. has been de-energized.
Action Text in display Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H4.
Present system status
ACCEPT? H4
"A"
Disablement
ACCEPT? U1
Scroll to menu U7.
Version and alarm counter
ACCEPT? U7
Press "A" to accept.
"A" Version: X.X.X
Alarm counter: YYY
Press "Return" to menu
U7.
"Return"
Version and alarm counter
ACCEPT? U7
Scroll or press "Return" to
menu H4.
"Return"
Present system status
ACCEPT? H4
Scroll or press "Return"