21.8 Re-Enable All Control, Ventilation, Extinguishing, Or
Interlocking Outputs (H2/B8)
Disabled outputs are listed in menu H4/U1.
When all outputs have been re-enabled, the LED "Disablements" (L8) will be extinguished,
if there are no other disablements.
If there is nothing to re-enable, --- List is empty --- will be shown.
Action Text in display Comments
"Access" Log on to FT128 as shown
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A" Disable zone
ACCEPT? B1
Scroll to menu B8. Re-enable all control, ventil, exting
or interlocking outputs ACCEPT? B8
"A" Re-enable type:0 0=Control 1=Ventilation
2=Exting 3=Interlocking ACCEPT?
Only disabled type(s) will
be shown. Press:
"0"=control output
"1"=extinguishing output
"2"=ventilation output
"3"=interlocking output.
Or, e.g. if only type 1 is disabled:
Re-enable type:0 1=Ventilation
ACCEPT?
Press 1
"A"
--- List is empty --- All types are re-enabled.
"Return"
Re-enable all control, ventil, exting
or interlocking outputs ACCEPT? B8
Scroll or press "Return" to
menu H2.
"Return" Disable or re-enable
ACCEPT? H2
Scroll or press "Return".