Operation Manual
FT128 Rev 2.4
96
21.9 Disable / Re-Enable Alarm Devices (H2/B9)
Disabled alarm devices are listed in menu H4/U1.
Outputs for alarm devices can be collectively disabled and re-enabled via this menu.
Disabled output will stay disabled, until re-enabled again via this menu.
When all outputs type Alarm devices have been disabled, the LEDs "Disablements" (L8)
and "Fault / Disablements Alarm devices" (L13) will be illuminated.
When all outputs type Alarm devices have been re-enabled, the LED "Fault /
Disablements Alarm devices" (L13) will be extinguished.
Note: This function for alarm devices is not the same as for push button "Silence alarm
devices" (P3) – unless the option Button "Silence alarm devices" disables alarm devices,
is selected in EBLwin System properties, see chapter "Silence Alarm devices", page 42.
This menu has higher priority than the push button "Silence alarm devices".
Action Text in display Comments
"Access"
Log on to FT128 as shown
in page 35.
Disable or re-enable
ACCEPT? H2
Disable zone
ACCEPT? B1
Scroll to menu B9 Disable / re-enable alarm devices
ACCEPT? B9
"A" Alarm devices in normal condition
Press ACCEPT to disable
Depending on the actual
status one of the texts will
be shown.
"A" Alarm devices disabled
Press ACCEPT to re-enable
"Return"
Disable or re-enable outputs for
routing equipment ACCEPT? B9
Scroll or press "Return" to
return to H2.
"Return"
Disable or re-enable
ACCEPT? H2
Scroll or press "Return".