FT128 Rev 2.4
82
19 Restart
A restart may delete some data in FT128. Below follows an explanation of the different
data, abbreviations and a table describing the different restart alternatives and how the
data respectively is affected (cold or warm restart).
FF = Fire alarms and Faults.
D = Disablements
FFD = Fire alarms, Faults and Disablements.
SSW = Sensor min. / max. values and performance factor, password, supervised
output calibration values and event log.
WASV = Week Average Sensor Values
SSD = Site Specific Data, i.e. all the installation programming created and
downloaded via EBLWin.
S/W = Software, i.e. the EBL128 system program.
The date & time and alarm counter value is stored in the memory of the real time clock,
i.e. the value will be retained also after the FT128 powered down.
Note: After any restart, a new week average sensor value will be calculated within 2
minutes, for all the Analogue smoke detectors
57
. Thereafter a new average sensor value
will be calculated each week.
19.1 Safe Shut Down
Safe shut down of control unit via menu H8/S7 will save the SSW data in a Flash ROM in
FT128. Before the first "Safe shut down" of the control unit, this memory is empty. After
each "Safe shut down" the latest SSW data is saved. (Safe shut down will not save the
week average sensor values)
When FT128 is powered up, a restart takes place and the RAM (working memory) will read
the SSW data saved in the Flash ROM.
19.2 Restart Table
Table 15 below describes the different reset alternatives and how the data is affected.
Table 15 Data affected by restart
Action
Data -
Deleted
Data - not
Deleted
Restart
code
Power down
58
and then power up
again. ("Cold restart")
SSW
FFD, WASV
SSD,
S/W
00
Via menu H8/S4 Safe shut down of
control unit. ("Cold restart")
FFD, WASV
SSD,
S/W, SSW
00 alt. 03
Automatically after download of site
specific data (SSD) via a PC & EBLWin.
("Warm restart")
FF, WASV, D
SSD,
S/W, SSW
25
Automatically after download of
S/W via a PC & EBLWin. ("Cold restart")
FFD, WASV
SSD,
S/W, SSW
03
Automatically due to external
disturbance. ("Cold restart")
FFD, WASV
SSD,
S/W, SSW
01, 02 alt.
04-20
57
During these 2 minutes, all fire alarms from analogue smoke detectors will be suppressed.
58
Both the power supply (mains) and the batteries are disconnected.