EasyManua.ls Logo

Panasonic Firetracker FT128 - Disable; Re-Enable Alert Annunciation Function (H2;B11)

Panasonic Firetracker FT128
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Manual
FT128 Rev 2.4
98
21.11 Disable / Re-Enable Alert Annunciation Function (H2/B11)
Normal function:
For alarm points / zones programmed for Alert Annunciation (via EBLWin) the AA function
is normally enabled via a time channel, e.g. enabled daytime (during working hours) and
disabled night time.
As an alternative, the AA function can be continuously enabled (always on).
Turned Off
Via this menu (H2/B11), it is possible to disable the AA function, i.e. the AA function will
be disabled for the alarm points / zones programmed for Alert Annunciation in spite of the
time channel being "on" or the programming being set as continuously enabled.
The AA function will stay disabled until re-enabled again via this menu.
Action Text in display Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B11. Disable / re-
enable alert annunciation function
ACCEPT?B11
"A"
Alert annunciation function is in normal operation.
Press ACCEPT to turn off
Depending on the actual
status, one of the texts will
be shown.
"A" Alert annunciation function turned off.
Press ACCEPT to set to normal
"Return"
Disable / re-enable alert annunciation function
ACCEPT? B11
Scroll or press "Return" to
menu H2
"Return"
De-activate alert annunciation function
ACCEPT? H2
Scroll or press "Return".
Note: Disabled Alert Annunciation function is not indicated by LED "Disablements" (L8).
The LED "Fault / Disablements Fire Brigade TX delay" (L16) turned off, is indicating that
the Alert Annunciation function is turned off by a time channel or is disabled via this menu.