21.5 Re-Enable Zone (H2/B5)
Disabled zones are listed in menu H4/U1.
Re-enabling via this menu (H2/B5) has higher priority than automatic re-enabling.
Zones disabled via the "New Zealand FB Bulgin key Silence Alarms" (outside switch), have
to be re-enabled via menu B5 or B6 before they can activate a new alarm.
When all zones have been re-enabled, the LED "Disablements" (L8) will be turned OFF, if
there are no other disablements
61.
Note: Alarm points that have been individually disabled via menu H2/B2 cannot be
collectively re-enabled via this menu. They have to be individually re-enabled.
If there is nothing to re-enable, --- List is empty --- will be shown.
Action Text in display Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H2 Disable or re-enable
ACCEPT? H2
"A" Disable zone
ACCEPT? B1
Scroll to menu B5 Re-enable zone
ACCEPT? B5
"A" Re-enable zone: 01
ACCEPT? L
L=A list in which you can
scroll.
Press "A" to accept. You
will stay in this list until all
zones are re-enabled or
press "Return" to menu
B5.
"A" (to re-enable)
or
"Return"
Re-enable zone
ACCEPT? B5
If more re-enabling shall
be done, continue like
above. If not, scroll or
press "Return" to menu
H2.
"Return" Disable or re-enable
ACCEPT? H2
Scroll or press "Return"
61
If zone control card is used, also the disabled zone LED will extinguish.