Operation Manual
FT128 Rev 2.4
97
21.10 Disable / Re-Enable Outputs for Routing Equipment
(H2/B10)
Disabled outputs are listed in menu H4/U1.
Outputs for routing equipment (Fire Brigade TX / fault TX) can be disabled and re-enabled
via this menu. Disabled output will stay disabled, until re-enabled again via this menu.
The function can be used during commissioning and testing of an installation, when only
local alarms are required but it can’t be used during normal operation. This menu must
not be used to disable routing equipment.
Disabled output is indicated by LEDs "Disablements" (L8) and "Fault / Disablements Fire
Brigade TX" (L15).
Action Text in display Comments
"Access"
Log on to FT128 as shown in
page 35.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B10
Disable / re-enable outputs for
routing equipment ACCEPT? B10
"A"
Routing equipment for FIRE: 1, FAULT:1
(1=enabled, 0=disabled) ACCEPT?
To move the cursor, press
"". Edit and/or press "A" to
accept.
e.g. “0”
“A”
All outputs to routing equipment for: FIRE is disabled /
FAULT is enabled
“A”
Routing equipment for FIRE:0, FAULT:1 (1=enabled,
0=disabled) ACCEPT?
“Return” Disable / re-enable outputs for routing equipment
ACCEPT? B10
Scroll or press "Return" to
return to H2.
“Return” Disable or re-enable
ACCEPT? H2
Scroll or press "Return".