EasyManua.ls Logo

Panasonic Firetracker FT128 - Disable Zone (H2;B1)

Panasonic Firetracker FT128
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Manual
FT128 Rev 2.4
88
21.1 Disable Zone (H2/B1)
When a whole zone is disabled, all alarm points within the zone are disabled.
Alarm points can be individually disabled.
Disabled zones can be automatically re-enabled or re-enabled via menu H2/B5.
Action Text in display Comments
"Access"
Log on to FT128 as shown
in page 35.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
"A"
Disable zone: 0 0
ACCEPT?
Write zone number
e.g. 01
Disable zone: 01
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling: 0 (0=No, 1=Yes)
Time: HH:MM ACCEPT?
Press "1" for auto re-
enabling and accept or
change the time (max. 24
hours). Press "A" to accept.
LED "Disablements" (L8)
will light up.
(Default is current time + 3 hours)
"A"
Zone 01 is disabled
"A"
Disable zone: 0 0
ACCEPT?
If more disablements
required, continue as above
otherwise, press "Return" to
menu B1.
“Return”
Disable zone
ACCEPT? B1
Scroll or press “Return” to
menu H2
“Return”
Disable or re-enable
ACCEPT? H2
Scroll or press “Return”

Table of Contents