EasyManua.ls Logo

Panasonic Firetracker FT128 - Disable Zone; Address (H2;B2)

Panasonic Firetracker FT128
150 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Operation Manual
FT128 Rev 2.4
89
21.2 Disable Zone / Address (H2/B2)
Up to 100 addressable alarm points (also addressable manual call points), connected to
the COM loop, can be individually disabled.
Disabled alarm points (zone address) are listed in menu H4/U1.
Disabled alarm points (zone address) can be automatically re-enabled or via menu
H2/B6.
Note: The sensor values for disabled analogue smoke detectors in NORMAL mode will
not be used for calculation of the week average sensor value, i.e. only the values saved
before and after the disablement will be used for this calculation.
Action Text in display Comments
"Access"
Log on to FT128 as shown in
page 35.
Scroll to menu H2.
Disable or re-enable
ACCEPT? H2
"A"
Disable zone
ACCEPT? B1
Scroll to menu B2.
Disable zone / address
ACCEPT? B2
"A"
Disable zone: 0 0 Address: 00
ACCEPT?
Write zone number
and address
e.g. 01 - 01
Disable zone: 01 Address: 01
ACCEPT?
Press "A" to accept.
"A"
Automatic re-enabling: 0 (0=No,1=Yes)
Time: HH:MM ACCEPT?
Press "1" for auto re-
enabling and accept or
change the time (max. 24
hours).
Press "A" to accept. LED
"Disablements" (L8) will
light up.
(Default is current time + 3 hours)
"A" Zone 01 address 01 is disabled
"A"
Disable zone: 0 0 Address: 00
ACCEPT?
If more disablements
required, continue as
above otherwise, press
"Return" to menu B2.
"Return"
Disable zone-address
ACCEPT? B2
Scroll or press "Return" to
menu H2.
"Return"
Disable or re-enable
ACCEPT? H2
Scroll or press "Return"

Table of Contents