Digital input 1
Function Pause
A0986
7.1.1
Status
Switch off delay
Alarm
Assignment
Active opened
10 s
On
Channel 1
Fig. 97: Setting [Digital input 1]
Pause
Parameter Adjustment range
Function Pause / Off / Pause Hold
Status Active opened / Active closed
Switch off delay 0 ... 1800 s
Alarm On/Off
Assignment Channel 1, channel 1+2
Setting [Digital input 2]
Sample water fault
Parameter Adjustment range
Function Off / Sample water fault
Status Active open / Active closed
Switch off delay 0 ... 1800 s
Assignment Channel 1, channel 1+2
Setting [Digital inputs]