P107 Near Blanking 
This parameter is the distance from the face of the transducer that is not 
measurable and is pre-set to the minimum value dependant on the 
Transducer (P101) selected. It should not be set to less than this figure, but 
can be increased, typically to ignore close in obstructions. 
Default Blanking Distance = 0.00m (0 ft) 
Default Blanking Distance = 0.125m (041 ft) 
Default Blanking Distance = 0.30m (0.98 ft) 
Default Blanking Distance = 0.30m (0.98 ft) 
Default Blanking Distance = 0.50m (1.64 ft) 
Default Blanking Distance = 0.60m (1.96 ft) 
Default Blanking Distance = 1.20m (3.93 ft) 
Default Blanking Distance = 0.20m (0.65 ft) 
Default Blanking Distance = 0.077m (0.25 ft) 
Default Blanking Distance = 0.077m (0.25 ft) 
*The signal emanates from the curved face of the radar, but for the purposes 
of measurement it is taken from the drip shield. 
P108 Far Blanking Distance 
This is the distance (as a percentage of the empty level P105) beyond the 
empty point that the unit will be able to measure, and by default is pre-set 
to 20% of the empty level. 
If the surface being monitored can be extended beyond the empty level 
(P105) then the far blanking distance can be increased to a max. of 100% of 
the empty level, provided it does not exceed the max range of the 
transducer being used.  This parameter is always entered as a % of the 
empty level.