EasyManuals Logo

Pulsar Ultra 4 User Manual

Pulsar Ultra 4
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #155 background imageLoading...
Page #155 background image
PULSAR MEASUREMENT
155
Display Parameters
Options
P800 Display Units
This parameter determines whether the reading displayed is in
Measurement Units (P104), or as a percentage of span.
OPTION
DESCRIPTION
1 = Measured (Default)
Display is in selected unit’s dependent in Mode
(P100)
2 = Percentage
Display is in percentage of span dependent in
Mode (P100)
P801 Decimal Places
This parameter determines the number of decimal places on the reading
during run mode. Minimum = 0 (No decimal places), Maximum 3 = (3
decimal Places). Default = 2 (2 decimal Places).
P802 Display Offset
The value of this parameter is added to the reading before it is displayed, in
Measurement Units (P104).
It does not affect the relay setpoints or the mA output, only the reading on
the display.
You could use this feature if for example you wanted to reference the
reading to sea level, where you would enter the distance between Empty
Level (P105) and sea level. If the empty level point is below sea level, then
enter a negative value.
P804 Display Conversion
The reading is multiplied by the value of this parameter before being
displayed. The default is 1.0, but if for example you wanted to display the
reading in yards, then set the Measurement Units (P104) to feet and set
P804 to 3.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Pulsar Ultra 4 and is the answer not in the manual?

Pulsar Ultra 4 Specifications

General IconGeneral
BrandPulsar
ModelUltra 4
CategoryMeasuring Instruments
LanguageEnglish

Related product manuals