Display Parameters 
Options 
P800 Display Units 
This parameter determines whether the reading displayed is in 
Measurement Units (P104), or as a percentage of span. 
P801 Decimal Places 
This parameter determines the number of decimal places on the reading 
during run mode. Minimum = 0 (No decimal places), Maximum 3 = (3 
decimal Places).  Default = 2 (2 decimal Places). 
P802 Display Offset 
The value of this parameter is added to the reading before it is displayed, in 
Measurement Units (P104). 
It does not affect the relay setpoints or the mA output, only the reading on 
the display. 
You could use this feature if for example you wanted to reference the 
reading to sea level, where you would enter the distance between Empty 
Level (P105) and sea level. If the empty level point is below sea level, then 
enter a negative value. 
P804 Display Conversion 
The reading is multiplied by the value of this parameter before being 
displayed. The default is 1.0, but if for example you wanted to display the 
reading in yards, then set the Measurement Units (P104) to feet and set 
P804 to 3.