ULTRA 4 INSTRUCTION MANUAL
162
P835 mA High Level
This parameter sets the level, distance, or space, depending on the selected
mA Out Mode (P831) at which the high mA output will occur (20mA).
Default = 6.00m
mA Limits
P836 mA Low Limit
This parameter sets the lowest level that the mA output will drop to, the
default is 0mA, but you can override this if the device you connect to cannot
for example accept less than 2mA, yet you want to use the 0-20mA range.
Default = 4.00mA
P837 mA High Limit
This parameter sets the highest level that the mA output will rise to, the
default is 20 mA, but you can override this if the device you connect to
cannot for example accept more than 18 mA, yet you want to use the 0-20
mA range. Default = 20.00mA