PULSAR MEASUREMENT 
 
121 
 
Alarms 
P2n0 = 1 (Alarm) 
The second parameter for each relay determines the function of the alarm. 
P2n1 – Relay Function 
Alarm is based on the level in the vessel, and the type of 
level alarm (P2n2) and two setpoints must be set (P2n3 & 
P2n4). Setpoints are entered in Display Units or % of span as 
referenced to Empty Level*. 
Alarm is based on the rate of change of level in the vessel, 
and the type of rate of change alarm (P2n2) and two 
setpoints must be set (P2n3 & P2n4). Setpoints are entered 
in Display Units per minute or % of span per minute and a 
negative value should be entered for a Rate Alarm on a de-
creasing level, and a positive value for an increasing level.  
Alarm is based on the temperature, and the type of 
temperature alarm ((P2n2) and two setpoints must be set 
(P2n3 & P2n4). The temperature used depends on the 
temperature source selected (P852). Setpoints are entered in 
o
C. 
Alarm is raised if the Failsafe Timer (P809) expires.  No 
setpoints required.  
Alarm is raised if the expires. No setpoints required.  
Alarm is raised when the service alarm date/time interval 
expires.  This is set in ‘System > Service Alarm > Date 
(P194) > Interval (P195).  The alarm trigger is automatic in 
the unit and is set at 12 noon, meaning that the alarm will 
activate at 12 noon on the date programmed into the unit 
when the service is now due.  No setpoints are required. 
Alarm is based on the Volume in the vessel and two 
setpoints must be set (P2n3 & P2n4). Setpoints are entered 
in Volume units.