PULSAR MEASUREMENT 
 
161 
 
Operation 
P831 mA Mode 
This parameter determines how the mA Output relates to what is measured. 
By default, it operates the same as the display (P100), but it can be set to 
operate as follows: 
Setpoint 
By default, the mA Output will represent the empty (0 or 4mA dependent 
on (P830) mA Range) and 100% of the operational span (20mA), but you 
may wish to have the output represent a section of the operational span.  
For example, the application has an operational span of 6 metres (19.68 ft), 
but output is to represent empty (0 or 4mA dependent on (P830) mA 
Range) to a level of 5 metres (20mA). If so P834 (Low Level) should be set 
to 0.00 metres and P835 (High Level) should be set to 5 metres (16.4 ft).  
Alternatively, the setpoints can be set to Flow units (P706) or Volume units 
(P606) depending on the system type and program used.  By default, these 
setpoints are in Measurement units (P104). 
P834 mA Low Level 
This parameter sets the level, distance, or space, depending on the selected 
mA Out Mode (P831) at which the low mA output will occur (0 or 4mA 
dependant on (P830) mA Range).  Default = 0.000m