Operation
P831 mA Mode
This parameter determines how the mA Output relates to what is measured.
By default, it operates the same as the display (P100), but it can be set to
operate as follows:
OPTION
DESCRIPTION
When Ultra Wizard = 1 Level/Volume, 2 Pump or 3 Flow
0 = Default
mA output relative to Mode P100
1 = Distance
mA output relative to Distance.
2 = Level
mA output relative to Level.
3 = Space
mA output is relative to Space.
When Ultra Wizard = 1 Level/Volume
5 = Volume
mA output is relative to Volume
When Ultra Wizard = 3 Flow
4 = OCM Head
mA output is relative to OCM Head
5 = OCM Flow
mA output is relative to OCM Flow
6 = Average Flow
mA output is relative to Average Flow
Setpoint
By default, the mA Output will represent the empty (0 or 4mA dependent
on (P830) mA Range) and 100% of the operational span (20mA), but you
may wish to have the output represent a section of the operational span.
For example, the application has an operational span of 6 metres (19.68 ft),
but output is to represent empty (0 or 4mA dependent on (P830) mA
Range) to a level of 5 metres (20mA). If so P834 (Low Level) should be set
to 0.00 metres and P835 (High Level) should be set to 5 metres (16.4 ft).
Alternatively, the setpoints can be set to Flow units (P706) or Volume units
(P606) depending on the system type and program used. By default, these
setpoints are in Measurement units (P104).
P834 mA Low Level
This parameter sets the level, distance, or space, depending on the selected
mA Out Mode (P831) at which the low mA output will occur (0 or 4mA
dependant on (P830) mA Range). Default = 0.000m