EasyManua.ls Logo

Pulsar Ultra 4 - Rectangular Broad Crested Weir Calculations

Pulsar Ultra 4
190 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
PULSAR MEASUREMENT
99
Rectangular Broad Crested Weir Calculations
Calculations
Absolute
If the flow calculation is to be absolute P702 = 1 the flow will be calculated
using the formula: q = (2/3)
1.5
C
e
b(gh
3
)
0.5
Where:
q = flowrate
Ce = discharge coefficient calculated by Ultra 4 P723
b = approach width P710
g = gravitational acceleration (nominal value = 980.66 cm/s
2
)
h = head
Ratiometric
If the flow calculation is to be ratiometric P702 = 2 the flow will be
calculated using the formula: q= q
cal
C
e
/C
ecal
(h
e
/h
ecal
)
1.5
Where:
q = flowrate
q
cal
= flowrate at maximum head P705
Ce = discharge coefficient calculated by Ultra 4 P723
Ce
cal
= discharge coefficient at maximum head
he = effective head
he
cal
= effective head at maximum head

Table of Contents

Related product manuals