The third parameter for each relay determines the assignment or 
condition of the relay, where required.  
P212, P222, P232 - Relay Alarm ID/Pump Group,  
P2n1 = 1 (Time) 
This parameter has no function and will not be displayed. 
P2n1 = 2 (Step Time)  
If the relay is selected for Step Time, then this parameter is used to assign 
the relay to the 0 = Open condition (increase level) or 1 = Close condition 
(decrease level).  
The fourth parameter, fifth parameter and sixth parameter are set to 
determine the switch points, “ON” and “OFF” for the relay and where 
required the order of start. See control function, table (P2n1) for further 
information. 
P2n1 =1 (Time) 
P2n3 - Relay Setpoint 1 
This parameter determines the “Time Period” that the relay will remain 
“ON”. Relay Setpoints are entered in Minutes. 
P2n4 - Relay Setpoint 2 
This parameter determines the “Cycle Time” for the operation of the relay. 
Relay Setpoints are entered in Minutes. 
See the appropriate relay function tables (P2n1) for further information. 
P2n1 = 2 (Step Time)  
P2n3 - Relay Setpoint 1 
This parameter will determine the “level” at which the relay will become 
active. Relay Setpoint 1 is entered in values of Measurement Units (P104) 
P2n4 - Relay Setpoint 2 
Relay Setpoints are entered in Seconds to set Drive Period, the time that the 
relay will remain ON. 
P2n5 - Relay Setpoint 3 
This parameter is used to determine the Limit Time between each Drive 
Period. Relay Setpoints are entered in Minutes, during which time the relay 
will remain OFF.