ULTRA 4 INSTRUCTION MANUAL
152
P715 Water Temperature
When P700 = 2, BS3680 Flume this parameter is used to enter the mean
water temperature in
0
C.
P717 Exponent
This parameter is used to enter the exponent value when:
P700 PMD Type = 1 Exponent and P701 Primary M.D = 7 Others.
P718 K Factor
This parameter is used to enter the K Factor when:
P700 PMD Type = 1 Exponent and P702 Calculation = 1 Absolute, see table
below for further details.
PRIMARY MEASURING DEVICE
P718 K FACTOR
P700 = 1 Exponent
P701 = 1 Supp. Rectangular Weir
Automatically
Calculated
P700 = 1 Exponent
P701 = 2 Trapezoidal
Automatically
Calculated
P700 = 1 Exponent
P701 = 3 Venturi Flume
Obtain value and enter
P700 = 1 Exponent
P701 = 4 Parshall Flume
Automatically
Calculated
P700 = 1 Exponent
P701 = 5 Leopold Lagco Flume
Automatically
Calculated
P700 = 1 Exponent
P701 = 6 V Notch
Automatically
Calculated
P700 = 1 Exponent
P701 = 7 Other
Obtain value and enter
P719 Throat Width
This parameter is used to select the Throat Width of the flume when: P700
PMD Type = 1 Exponent and P701 = 4 Parshall Flume. After selecting the
Throat Width, the Exponent P717 and K Factor P 718 will be set
automatically.