Relay Outputs 
All four of the relays can be programmed for a variety of alarms, pump 
control, or other process functions. Three relays have contacts rated at 5A at 
240V AC. The fourth is a low power solid state SPNO isolated relay, intended 
to be suitable for pulse counter functions. 
All connections should be fused or protected such that the short circuit 
capacity of the circuits to which they are connected is limited so that they do 
not exceed the relay rating. 
Current Output 
This is an isolated (floating) mA output (to 150 V), of 4 - 20mA or 0 - 20mA, 
and the load should not exceed 500 
. 
RS2323 Serial Interface 
If required, you can connect to the serial interface to operate your Ultra 4 
remotely. 
Wire/cable ratings & sizes (Copper conductors)