ULTRA 4 INSTRUCTION MANUAL
68
Relay Setpoints Table
The default values used for determining the relay setpoints, when setting
Alarms and Control relays, via the Quick Setup menu are entered as a % of
span and are as follows:
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Pump Down
One
Pump 1
50%
20%
Pump Down
Two
Pump 1
Pump 2
50%
70%
20%
20%
Pump Down
Three
Pump 1
Pump 2
Pump 3
50%
60%
70%
20%
20%
20%
Pump Down
Four
Pump 1
Pump 2
Pump 3
Pump 4
40%
50%
60%
70%
20%
20%
20%
20%
APPLICATION
NO. OF CTL
RELAYS
CTL RELAY
NUMBER
ON
SETPOINT
OFF
SETPOINT
Control Up
One
Control 1
50%
20%
Control Up
Two
Control 1
Control 2
50%
30%
20%
20%
Control Up
Three
Control 1
Control 2
Control 3
50%
40%
30%
20%
20%
20%
Control Up
Four
Control 1
Control 2
Control 3
Control 4
60%
50%
40%
30%
20%
20%
20%
20%
RELAY
FUNCTION
RELAY ID
ON
SETPOINT
OFF
SETPOINT
Alarm
HiHi
90%
85%
Alarm
High
85%
80%
Alarm
Low
10%
15%
Alarm
LoLo
5%
10%

Table of Contents