108 Rockwell Automation Publication IASIMP-QS005H-EN-P - April 2016
Chapter 4 SmartGuard™ 600 Controllers Logic Integration
Configure SmartGuard 600 Local Inputs and Test Outputs
The SmartGuard 600 local input and test output configuration is dependent on the input device type, input relationship,
and fault detection requirements. All the inputs and test outputs are pre-configured for volt-free contact devices to
perform the diagnostics necessary to achieve the safety category level indicated by the pre-configured *.dnt file name. Use
the following steps and table recommendations to configure the safety inputs and test outputs.
Table 10 - Typical Safety Input Device Configuration Parameters
Input Device Type Category
Channel
Mode Test Source On-Off Delay Time Off-On Delay Time
Dual
Channel
Mode Discrepancy
Time
Error
Latch
Time
Test
Output
Mode
Volt-free contacts
(2 Normally Closed)
4 Test pulse
from test
output
Ch A: Test
Output(x),
Ch B: Test
Output(x+1)
(1)
Cycle Time x 2
(2)
Cycle Time x 2 Dual Channel
Equivalent
100 1000 Safety
Pulse Test
3Used as
safety input
Not Used Cycle Time x 2 Cycle Time x 2 Dual Channel
Equivalent
100 1000 Safety
Volt-free contacts
(1 Normally Closed,
1 Normally Open)
4 Test pulse
from test
output
Ch A: Test
Output(x),
Ch B: Test
Output(x+1)(1
)
Cycle Time x 2 Cycle Time x 2 Dual Channel
Equivalent
100 1000 Safety
Pulse Test
3Used as
safety input
Not Used Cycle Time x 2 Cycle Time x 2 Dual Channel
Equivalent
100 1000 Safety
Volt-free contacts
(1 Normally Closed)
2 Test pulse
from test
output
Test Output(x) Cycle Time x 2 Cycle Time x 2 Single
Channel
N/A 1000 Safety
Pulse Test
2 channel OSSD
(Output Signal
Switch Device)
4
(3)
Used as
safety input
Not Used 0 0 Dual Channel
Equivalent
0 1000 Not Used
3
(4)
Used as
safety input
Not Used 0 0 Dual Channel
Equivalent
0 1000 Not Used
1 channel OSSD 2
(5)
Used as
safety input
Not Used 0 0 Single
Channel
N/A 1000 Not Used
(1) Dual channels require different test sources.
(2) Time must be multiple of cycle-time.
(3) Must be a Cat. 4 capable OSSD.
(4) Must be a Cat. 3 capable OSSD.
(5) Must be a Cat. 2 capable OSSD.