Rockwell Automation Publication IASIMP-QS005H-EN-P - April 2016 53
GuardLogix® Controllers Logic Integration Chapter 3
8. Check the module definition by clicking Change.
The pre-configured Guard I/O module configurations that you added in steps 1…4 include the settings required
to work with the Guard I/O faceplates and AOI instructions.
These required di
g
ital I/O configuration settings include:
Set Input Status to ‘Combined Status - Muting’ for all modules
Set Output Data to ‘Combined’ for all modules with both safety inputs and outputs
Set Output Data to ‘Combined Status’ for all modules with only safety outputs