act as the delayed ones. Up to 255 seconds can be programmed. If the value 0 is
programmed, the ENTRY DELAY programmed for the partition will be treated as the DELAY
ACTIVATION TIME
. If the value 0 is programmed for both the zone and the partition, violation
of the zone will have no effect.
Waiting time – the time counted from the moment of violating the 4. DOUBLE KNOCK type
zone. If the zone is violated again during the waiting time, it will trigger alarm. Up to 255
seconds can be programmed. Programming the value 0 means that the WAITING TIME will
be 30 seconds.
In the LCD keypad, the ENTRY DELAY, DELAY ACTIVATION TIME and WAITING TIME
parameters are programmed as the ALARM DELAY.
Arm mode – the armed mode activated after violating the 13. ARM/DISARM or 14. ARMING
type zone. You can select either fully arming, day arming or night arming.
Event – number of the event that will be written into the control panel memory and can be
reported to the monitoring station upon violation of the 19. TROUBLE type zone. You can
enter the following values for the corresponding codes of alarm events:
1 – 201 Low water pressure
2 – 202 Low CO2
3 – 203 Gate valve sensor
4 – 204 Low water level
5 – 205 Pump activated
6 – 206 Pump failure
51 – 151 Gas detected
52 – 152 Refrigeration
53 – 153 Loss of heat
54 – 154 Water leakage
55 – 155 Foil break trouble
56 – 156 Day trouble
57 – 157 Low bottle gas level
58 – 158 High temperature
59 – 159 Low temperature
61 – 161 Loss of air flow
62 – 162 Carbon monoxide (CO) detected
63 – 163 Tank level trouble
Entering a different value means that the zone violation will trigger the trouble signaling,
but no alarm events from zone will be written to the event log.
Wiring type – type of detector and the method of its connection (zone configuration):
no detector – no detector is connected to the zone,
NC – the zone supports a detector of NC (normally closed) type,
NO – the zone supports a detector of NO (normally open) type,
EOL – the zone supports a detector of NO or NC type with EOL resistor in the circuit,
2EOL/NO – the zone supports a detector of NO type with two EOL resistors in the circuit,
2EOL/NC – the zone supports a detector of NC type with two EOL resistors in the circuit,
roller – the zone supervise a roller shutter detector,
vibration – the zone supervise a vibration detector (also NC type detector).