SATEL VERSA 35
8. Zone type.
9. Alarm delay [ARM MODE for 13. ARM/DISARM and 14. ARMING type zones, and the EVENT
for the 19. TROUBLE type zone].
10. Max. violation time.
11. Max. no violation time.
12. Zone options.
13. Zone name [only in LCD keypad].
6.3 Zone parameters
Fig. 9. DLOADX program: programming the zone parameters in “VERSA – Structure”
window.
Zone name – individual name of zone (up to 16 characters).
Partition 1 / Partition 2 – partition to which the zone is assigned. The zone must be
assigned at least one partition, for its status to be supervised.
Entry delay – the time counted from the moment of violating the 0. E
NTRY/EXIT or 1. ENTRY/EXIT
FINAL
type zone, which makes disarming possible before triggering the alarm. Up to 255
seconds can be programmed. If the value 0 is programmed, the ENTRY DELAY programmed
for the partition will be taken into account. If the value 0 is programmed for both the zone and
the partition, the zone will act as an instant one.
Delay – the time counted from the moment of violating the 2. ENTRY/EXIT ROUTE type zone, if
it acts as a delayed one. Up to 255 seconds can be programmed. If the value 0 is
programmed, the ENTRY DELAY programmed for the partition will be treated as the DELAY
TIME
. If the value 0 is programmed for both the zone and the partition, the zone will act as
an instant one.
Delay activation time – the time counted from the moment of violating the 18. ENTRY ROUTE
ENABLING
type zone. During countdown of this time, the 2. ENTRY/EXIT ROUTE type zone will