SATEL VERSA 83
– EVENTS AMOUNT LIMITING (in the DLOADX program, the option is available in the
reporting options),
– BLOCK AFTER 3 UNKNOWN CODES/CARDS.
disable the global options:
– TAMPER ALARM ALWAYS AUDIBLE,
– ARM EVEN IF NOT READY AFTER EXIT DELAY.
program the AC loss time after which a trouble will be reported to be no longer than 60
minutes (AC LOSS REPORT DELAY global parameter),
in case of arming by means of timers, program the suitable auto-arming delay in partitions
so that the system users can be warned of the automatic arming,
program the entry delay to be no longer than 45 seconds,
enable the AUTO-RESET 3 option for all burglary zones,
disable the A
LARM ON EXIT DELAY END option for alarm zones beyond the exit route,
enable the B
YPASS DISABLED option for tamper, panic and trouble zones,
remember that the operation time of acoustic sirens should be minimum 90 seconds and
maximum 15 minutes (which requires suitable configuration of the cut-off time of alarm
signaling outputs).
14. Control panel firmware update
1. Download the update program for control panel firmware from www.satel.eu.
2. Connect the control panel RS-232 (TTL) port with the computer port (for example, using
the USB-RS converter offered by SATEL).
3. Update the control panel firmware, using one of the methods described below.
When the firmware update is running, the control panel does not execute its normal
functions.
14.1 Standard update procedure
1. Use the keypad to enter the service mode (enter the service code and press , and
then ).
2. Press in turn
. The STARTER function will start. The control panel will
be waiting until communication with the firmware updating program is established (you
can terminate the STARTER function by pressing
).
3. Run the update program for control panel firmware.
4. Click on the button.
5. In the window that will be displayed, indicate the COM port of the computer to which the
control panel is connected and click “OK”. The firmware updating program will establish
communication with the control panel.
6. When a prompt window is displayed asking you whether to continue the firmware update,
click “Yes”. The control panel firmware will be updated.
14.2 Emergency update procedure
If the control panel does not support keypads, does not accept the service code, etc., you
can make use of the following procedure to update the control panel firmware.

Table of Contents