Hardware Manual for the PCD2.M5 Series│Document 26/856; Version EN 12│2014-07-24
Saia-Burgess Controls AG
Analogue input modules
Input/output (I/O) modules
6-51
6
Connection diagram for PCD2.W210, two-wire transducer
E1
E0
GND
PCD2.W210
4...20 mA*
0...20 mA
ϑ
υ
24 VDC
Tempera-
ture
Speed
Input filter
+
E2
*4...20 mA over user program
Two-wiretransducers(0..20mAand4...20mAtransmitters)needa24VDC supply in
the measuring trunk.
Connection concept PCD3.W220 Pt1000 / Ni1000
Connection concept PCD3.W220Z02 NTC10
-
9 8 7 6 5 4 3 2 1 0
- E7 E6 E5 E4 E3 E2 E1 E0
PGND
PCD2/3.W220
Pt/Ni 1000
Earthing bar
Shield
Resistance
of
measurement
Resistance
of
measurement
Resistance
of
measurement
of
Shield
Shield
Shield
max. 25 cm
min. 2.5 mm2
Power PCD