General Diagram
INTECONT® Tersus Belt weigher, Instruction Manual
Schenck Process Group
BV-H2464GB, 1234
- 13 -
Display filters
▪ For feed rate, belt load and belt speed
Maintenance guidelines by overlaying an event in the display
▪ for the voltage supply's operating time, the scale's operating time and the next zero setting.
Calibration
▪ It is not necessary to calibrate the pick-up input. Certain design data such as on the load cells, velocity
sensors and conveyor belt inclination must be entered. The system uses this data to calculate all stan-
dardizations required for the displays. It can be controlled or readjusted using two different methods.
▪ Control with material: the result of a material inspection is entered into the system and it serves to cor-
rect the measurement result.
▪ Control with calibration weight: standardization is controlled or can also be corrected if the technical data
(such as the lever ratio or belt conveyor inclination) is not precisely known.
In later operation, the program also becomes suitable for verifying mechanical changes such as the
weighing platform being twisted due to movement of the foundations.