P06.09 Limit: Speed MIN
Default: 5 % V
Min: -10 % V Max: 200 % V
Lower limit for belt speed.
Reference: P02.05 Nominal Speed
P06.10 Event: Speed MIN
Default: W2
Event Group: LO Number: 04
The belt speed is less than the minimum value set in Limit: Speed MIN
P06.11 Limit: Speed MAX
Default: 120 % V
Min: -10 % V Max: 200 % V
Upper limit for belt speed.
Reference: P02.05 Nominal Speed
P06.12 Event: Speed MAX
Default: W2
Event Group: HI Number: 04
The belt speed is greater than the maximum value set in Limit: Speed MAX
13.3.2.7
13.3.2.713.3.2.7
13.3.2.7
Parameter Block
Parameter BlockParameter Block
Parameter Block
07
0707
07
-
--
-
Filters
FiltersFilters
Filters
The parameters of this group define the time constants of the filters for measurement and display.
All of the filters are 1st order (exponential), meaning that after a discontinuous signal change approx. 2/3 of
the final value will have been reached once the preset time has elapsed.
Long times result in a smooth, slowly-updating display.
P07.01 Filter: Actual Flow Rate
Default: 3 s
Min: 0 s Max: 600 s
Filter time constant for the display and for outputs of the actual feed rate at the operating
console, EasyServe and all fieldbuses. Has no effect on the feeder regulation.
P07.02 Filter: Actual Flow Rate analog
Default: 3 s
Min: 0 s Max: 600 s
Filter time constant for the actual feed rate analog output.