Parameters
INTECONT® Tersus Belt weigher, Instruction Manual
Schenck Process Group
BV-H2464GB, 1234
- 71 -
P05.09 Speed Range
Default: 20 mA
Min: 0 mA Max: 1000 mA
The output flow for the value of the belt speed of 100 %.
Reference: P02.05 Nominal Speed
Also refer to: P05.07 AO: Speed
13.3.2.6
13.3.2.613.3.2.6
13.3.2.6
Parameter Block
Parameter BlockParameter Block
Parameter Block
06
0606
06
-
--
-
Limit Values
Limit ValuesLimit Values
Limit Values
The parameters of this group define the limits for process values and specify the event classes of the asso-
ciated events.
Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.
P06.01 Limit: Actual Flow Rate MIN
Default: 5 % Io
Min: -10 % Io Max: 200 % Io
Lower threshold for the actual feed rate.
Reference : P02.02 Nominal Flow Rate
P06.02 Event: Actual Flow Rate MIN
Default: W2
Event Group: LO Number: 02
The actual feed rate is lower than the minimum value Limit: Actual Flow Rate MIN.
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low
P06.03 Limit: Actual Flow Rate MAX
Default: 120 % Io
Min: -10 % Io Max: 200 % Io
Upper threshold for the actual feed rate.
Reference : P02.02 Nominal Flow Rate