Parameters
INTECONT® Tersus Belt weigher, Instruction Manual
Schenck Process Group
BV-H2464GB, 1234
- 71 -
P05.09 Speed Range
Default: 20 mA
Min: 0 mA Max: 1000 mA
The output flow for the value of the belt speed of 100 %.
Reference: P02.05 Nominal Speed
Also refer to: P05.07 AO: Speed
13.3.2.6
13.3.2.613.3.2.6
13.3.2.6
Parameter Block
Parameter BlockParameter Block
Parameter Block
06
0606
06
-
--
-
Limit Values
Limit ValuesLimit Values
Limit Values
The parameters of this group define the limits for process values and specify the event classes of the asso-
ciated events.
Events that can only occur with regular feed operation are only monitored 10 s after beginning feed opera-
tion.
P06.01 Limit: Actual Flow Rate MIN
Default: 5 % Io
Min: -10 % Io Max: 200 % Io
Lower threshold for the actual feed rate.
Reference : P02.02 Nominal Flow Rate
P06.02 Event: Actual Flow Rate MIN
Default: W2
Event Group: LO Number: 02
The actual feed rate is lower than the minimum value Limit: Actual Flow Rate MIN.
Possible causes:
- no bulk material
- disturbance forces from force shunts or pressures acting on the weighing equipment
- feed rate setpoint too low
P06.03 Limit: Actual Flow Rate MAX
Default: 120 % Io
Min: -10 % Io Max: 200 % Io
Upper threshold for the actual feed rate.
Reference : P02.02 Nominal Flow Rate

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Schenck process Intecont Tersus Beltweigher and is the answer not in the manual?

Schenck process Intecont Tersus Beltweigher Specifications

General IconGeneral
BrandSchenck process
ModelIntecont Tersus Beltweigher
CategoryControl Panel
LanguageEnglish

Related product manuals