Parameters
BV-H2464GB, 1234
- 88 -
INTECONT® Tersus Belt weigher, Instruction Manual
Schenck Process Group
P14.03 Event: Tachometer Input
Default: A
Event Group: CA Number: 02
The signals at the feeder drive's impulse speedometer input are outside of the specified
range.
Possible causes:
- there is a fault in the speed impulse sensor cable (check the shielding and the wiring).
- the sensor has been incorrectly calibrated
P14.04 Event: NAMUR Error Tacho
Default: A
Event Group: WE Number: 09
A short-circuit or break in the cable to the velocity sensor.
The internal velocity value is set to 0 if a NAMUR error occurs.
The frequency display (service value) is still active.
The event message has to be set to IG if connecting up other equipment (not NAMUR).
External NAMUR adapters, resistor circuitry etc. are not required.
P14.05 Event: NAMUR Error Sensor
Default: W1
Event Group: WE Number: 10
The sensor signal at the input exceeds the permissible level.
Possible cause:
- cable to the sensor is broken
- the sensor is faulty
- there is a short circuit in the cable connection
- an external signal sensor is outputting the incorrect signal level
P14.06 Event: Error LC Input
Default: A
Event Group: CA Number: 01
The load cell cable is improperly connected, not connected or has been interrupted. The
load cell may be faulty.
Steps to take:
- check the cabling and the load cell
- check the load cell
Note:
The power supply must be switched off and on again if the scales still cannot be switched
on even after the error has been rectified.