Parameters
INTECONT® Tersus Belt weigher, Instruction Manual
Schenck Process Group
BV-H2464GB, 1234
- 91 -
P15.04 Linearization S2
Default: 50 % Q
Min: 0.01 % Q Max: 1000 % Q
Linearization point 2.
Otherwise as P15.02 Linearization S1
P15.05 Linearization I2
Default: 50 % Q
Min: 0.01 % Q Max: 1000 % Q
Linearization point 2.
Refer to P15.03 Linearization I1 for a description
P15.06 Linearization S3
Default: 75 % Q
Min: 0.01 % Q Max: 1000 % Q
Linearization point 3.
Otherwise as P15.02 Linearization S1
P15.07 Linearization I3
Default: 75 % Q
Min: 0.01 % Q Max: 1000 % Q
Linearization point 3.
Refer to P15.03 Linearization I1 for a description
P15.08 Linearization S4
Default: 100 % Q
Min: 0.01 % Q Max: 1000 % Q
Linearization point 4.
Otherwise as P15.02 Linearization S1
P15.09 Linearization I4
Default: 100 % Q
Min: 0.01 % Q Max: 1000 % Q
Linearization point 4.
Refer to P15.03 Linearization I1 for a description
P15.10 Event: Linearization Error
Default: W2
Event Group: CA Number: 05
Not a monotonically increasing curve.
A monotonically increasing compensation curve is monitored when:
- linearization is switched on,
- a parameter is altered