8021823/126P/2018-12-17 • © SICK AG • Subject to change without notice 63
Operation via Ethernet (Ethernet interface)
Field "MF1, Threshold
distanceunderow"
Requirements for the display
Parameter "MF1 activation": Option "Enable"
Parameter "Function": Option "Distance"
Parameter Description
Threshold
distance
Enter switching threshold for the multifunction output MF1.
Read/Write access
Read and write
Input value
–300000 ... 300000
Unit
mm
Factory setting
1990
Hysteresis
distance
Enter hysteresis for switching threshold for the multifunction
output MF1.
Read/Write access
Read and write
Input value
1 ... 300000
Unit
mm
Factory setting
10
Table 38: Page "Parameter settings" – eld "MF1, Threshold distance underow"
Field "MF1, Threshold velocity
exceeded"
Requirements for the display
Parameter "MF1 activation": Option "Enable"
Parameter "Function": Option "Velocity"
Parameter Description
Threshold
velocity
Enter switching threshold for the multifunction output MF1.
Read/Write access
Read and write
Input value
0 ... 15000
Unit
mm/s
Factory setting
5000