8021823/126P/2018-12-17 • © SICK AG • Subject to change without notice 89
PROFINET IO-interface
Module parameter "MF1"
Name Description
[MF1] Active
State
Select switching level for input and output MF1.
Value range
• Low
• High
Standard value
• Low
[MF1 Distance]
threshold [mm]
Enter value of the distance threshold in "mm".
Value range
• –300,000 ... 300,000 mm
Standard value
• 1,990 mm
[MF1 Distance]
Hysteresis [mm]
Enter hysteresis of the distance threshold in "mm".
Value range
• 1 ... 300,000 mm
Standard value
• 10 mm
[MF1 Speed]
Threshold
Enter speed threshold.
Value range
• 0 ... 15,000 mm/s
Standard value
• 5,000 mm/s
[MF1 Speed]
Mode
Select direction for detection in which the speed is exceeded.
Value range
• Negative direction [–]
• Positivedirection[+]
• Bothdirections[+/–]
Standard value
• Bothdirections[+/–]
[MF1 Service]
Laser Warning
The output switches when the laser module emits a warning.
Value range
• O
• On
Standard value
• On