INSTALLATION
3.5.6 Terminal box wiring
Table 6: Power supply of terminal box
Table 7: Terminal box wiring Table
PE
N 85 ... 264 V AC
L 45 ... 65 Hz
Terminal Id. VISIC100SF analog VISIC100SF system bus
1 +24 V DC +24 V DC
2 +24 V DC +24 V DC
3 Ground (GND) Ground (GND)
4 Ground (GND) Ground (GND)
5 DO1 - COM Maintenance Request Common RS-485 A
[1]
6 DO1 - NO Maintenance request Normally Open RS-485 A
[1]
7 DO2 -COM Malfunction Common RS-485 B
[1]
8 DO2 - NC Malfunction Normally Closed RS-485 B
[1]
9 DO3 - COM Not used RS-485 GND
[1]
10 DO3 - NO Not used RS-485 GND
[1]
11 + AO1 + visibility PROFIBUS-DP A
[2]
12 - AO1 - visibility PROFIBUS-DP A
[2]
13 + AO2 + gas concentration (CO,NO or NO
2
)PROFIBUS-DP B
[2]
14 - AO2 - gas concentration (CO,NO or NO
2
) PROFIBUS-DP B
[2]
15 + AO3 + gas concentration (CO,NO or NO
2
)
16 - AO3 - gas concentration (CO,NO or NO
2
)
17, 18,
19, 20
Not used Not used
[1]When connected via RS-485, terminals 5 + 6, 7 + 8 and 9 +10 must be connected with
a jumper.
[2]When connected via PROFIBUS, terminals 11 + 12 and 13 + 14 must be connected with
a jumper.
Observe the configuration of the analog outputs when using gas sensors, see “Activat-
ing/deactivating the heating (optional)”, page 65.