57
8017171/115Z/V3-0/2019-01/ SICK OPERATING INSTRUCTIONS | VISIC100SF
Subject to change without notice
VISIC100SF MENU NAVIGATION
5.5 Setting bus parameters
Menu item “Bus” serves to manage the parameters for the Modbus, PROFIBUS and TAD
control unit interfaces. A change to the bus system is first effective after a restart.
5.5.1 Setting the PROFIBUS address in “PB ID”
The configured address is assigned to the VISIC100SF after a restart when the device is
connected as “slave” in a PROFIBUS-DP system. Submenu item “PB ID” serves to manage
the PROFIBUS address. The valid address range is between 0 ... 126.
Arrow buttons: Increase and decrease the digits.
“Set” button: Activate next digit.
Fig. 40: Entering the PROFIBUS address
Press “Reset” to restart, see “Measuring unit - circuit board with display and keypad”,
page 17.
Submenu item “PB ID” is only available when the VISIC100SF has a PROFIBUS-DP
module installed.
RUN
X
XXX
Set
SET
Maint
Esc
Set
SET
PB ID
Esc
Set
2 s
xxx
>
>
...
...
SET
Bus
Set
>
>
-n +n
»
»
1.
2.
Set
3.
xxx
»
»
4.
1. - 3.
Esc
When the bus address has been entered completely, pressing “Set” switches the menu
back directly to the “Bus” main menu.